ANALOG UNIVERSAL MODULE HART FOR ZONE 1 / CIASS I, DIV. 1 SERIES 9468/32

HART Analog Universal Module 9468/32 Series for Zone 1 and Class I, Div. 1 has eight channels that can be used exclusively for I.S. operates two/three-wire HART transmitters, four-wire transmitters, or control valves/positioners with 0/4 to 20 mA signals. HART communication is two-way. All inputs/outputs are short-circuit-proof, galvanically isolated from the system, and individually monitored for line faults. – Eight channels can be used individually as inputs or outputs – Intrinsically safe Ex ia inputs/outputs with line error monitoring and LED error indicators for each channel – hot swap Modules in Zone 1 and Type I, Div. first